LLPD d24z up to 24 kV

  • Protection against:
Direct Lightning Strike,
Induced overvoltage,
Back Flashover

  • Highest voltage for equipment, kV24
  • Maximum prospective fault current, kA5.0
  • Lightning discharge capability, C2.8
  • Installation1, 2 or 3 pcs per pole
post, pin-post insulation with d10z
Electrical line parameters

Highest voltage for equipment*, kV

24

Maximum prospective fault current, kA

5

External air gap, mm

60-80

50% flashover voltage (80 mm air gap), kV

<150

Power frequency withstand voltage**, kV (wet/dry)

40/50


Lightning parameters

Lightning discharge capability (200 μs)***, C

2.8

High current impulse (4/10 μs), kA

65

Maximum quenching lightning current, kA

20 (8/50µs)

Minimum withstand amount of operations

10


General Parameters

Additional power losses on the line, %

0

Average expected lifespan, years

30

UV resistance****, h

1000

Eight, kg

2.8

Maintenance

1 visual verification/year


* According to IEC 60038, ** According to IEC 60071-1, *** According to IEC 60099-8, **** According to ISO 4892-2, method A, IEC 62217
Examples of installation methods