CONDUCTOR DIAMETER RANGE, mm | 5 to 25 35 to 300 mm |
INSTALLATION ON ТНЕ CONDUCТOR | Terminals, 13.5 mm hole in series |
MAXIMUM DISTANCE BETWEEN DISPLAY AND SENSOR | 20 m |
MINIMUM DISCHARGE PEAK CURRENT DETECTED - 8/20us waveform - IEC 62561-6 | 200 A |
MAXIMUM DISCHARGE PEAK CURRENT DETECTED - 10/350us waveform - IEC 62561-6 | 100 kA |
WAVEFORM REGISTRATION RESPONSE ТIМЕ | 1.3 µs |
MINIMUM TIME BETWEEN 2 STROKE FOR REGISTRATION, RESPONSE TIME | 10 µs |
VOLTAGE DROP ON TERMINALS | < 1 V |
LONG DURATION CURRENT WITHSTAND CAPABILITY | 2500A for 4ms |
HIGH CURRENT WITHSTAND CAPABILITY | 100 kA |
FREQUENCY, Hz | 47 to 63 |
IMPULSE CURRENT РЕАК MEASUREMENT | YES |
IMPULSE DURATION/ IMPULSE POLARIТY | YES |
MINIMUM DISCHARGE РЕАК CURRENT MEASURED - 8/20 us waveform - IEC 62561-6 | 200 A |
MAXIMUM DISCHARGE РЕАК CURRENT MEASURED - 10/350 us waveform - IEC 62561-6 | 40 kA |
РЕАК LIGHTNING CURRENT ACCURACY 8/20us | 10% |
FOLLOW CURRENT / GROUND FAULT RANGE | 70 to 10 000 A |
FOLLOW CURRENT / GROUND FAULT (50/60Hz) ACCURACY | 10% |
ТОТАL LEFТ THROUGH l2t | YES |
CHARGE RANGE | 0 to 65C |
ТОТАL LEAKAGE CURRENT | 50 µA to 50 mA |
ACCURACY (at Tamb ≤40 °С) | ±10% |
SURFACE POLLUTION & HUMIDIТY INGRESS DETECTION (UNDER EVALUATION) | YES |
THIRD HARMONIC LEAKAGE CURRENT | 50-5000 µA |
ACCURACY (at Tamb ≤ 40 °С) | ±15% |
RESISTIVE LEAKAGE CURRENT | 50-5000 µA |
ACCURACY (at Tamb ≤40 °С) | ±15% |